Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/29/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A SEDIMENT TRAP AT GAS ENTRY TO APPLIANCE 2) GAS FLEXES ARE NOT TO BE REVERSED 3) PROVIDE PETITION OF APPEAL FORM SIGNED BY CITY OF TUCSON ON SITE AT TIME OF INSPECTION 4) PROVIDE A PLUG IN THE DRAIN PAN 5) PROVIDE A NIPPLE WITH NO THREADS ON DISCHARGE END OF 125# PRESSURE RELIEF DEVICE AT EXTERIOR 6) WHEN VENT FROM WATER HEATER IS WITHIN 10' OF COOLER INTAKE IT SHALL TERMINATE 3' ABOVE TOP OF COOLER INTAKE WITH APPROVED DBL WALL VENT PIPE AND CAP |