Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08PL00625
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2008 | PLUMBING - FINAL | Approved | ||
05/28/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. DOOR BEHIND SNACK BAR LOCKED -- STAFF OPENED THE DOOR 2. EXPANSION TANKS REQUIRE SUPPORT, ESPECIALLY WHEN CONNECTED TO THE TANK WITH A FLEX CONNECTOR 3. CONTRACTOR TO PAY REINSPECTION FEE |
|
05/12/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - BOTH WATER HEATERS REQUIRE EXPANSION TANKS - SEE NOTE #2 FROM 4/21/08 - CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE |
|
04/21/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAKE PROPER ELECTRICAL CONNECTION AT SNACK BAR HEATER 2. COMMERICAL WATER HEATERS REQUIRE EXPANSION TANKS T&P RELIEF DRAIN TO BE GRAVITY TYPE (NO BACKPITCH ALLOWED) |