Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08OT02495
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2008 | FIRE - FINAL | Approved | ||
11/13/2008 | FIRE - FINAL | Denied | Not approved 11/13/08. Need Fire alarm final. |
|
11/06/2008 | FIRE - FINAL | Denied | 1.) Metal double-door installed for added security at main entrance/exit has been allowed provided the doors be locked in the open position at all times when the building is occupied. A sign idicating as such shall be posted on the doors. Failure to comply will result in the requirement of installing panic hardware on the doors. 2.) Remove the keyed-locking device from metal doors and provide thumb-turning locks. 3.) Extension cords are to be for temporary use only. 4.) Cover plates a.) mezzanine area. b.) behind the stage area. c.) production area. 5.) Remove slide-bolt locking devices from exterior doors. 6.) Cover opening in wall located in the "Production" area. 7.) Blanks for electrical panels a.) production area b.) electrical room. 8.) Portable extinguisher in the production area needs servicing . 9.) Replace ceiling tile in the tool shop area. 10.) Provide Fire Retartant certificate for drapes. 11.) Protect opening into the backstage area. 12.) Replace ceiling tiles in the backstage area. 13.) Repair emergency back-up lights in the classrooms area. 14.) Lable door to riser room. "RISER ROOM' |