Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2009 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
| 09/24/2008 | CERTIFICATE OF OCCUPANCY | Partial Approval | THE NEW USE OF THIS BUILDING CONSTITUTES A CHANGE OF OCCUPANCY. THEREFORE THIS COMPLEX WILL NEED TO BE SPRINKLERED PER THE INTERNATIONAL FIRE CODE. ALSO ELEMENTS THAT ARE NOW USED DIFFERENTLY THAN THE ORIGINAL R-2 DESIGNATION WILL NEED TO COMPLY WITH SECTION 3409.4 ACCESSIBILITY REQUIREMENTS OF THE 2006 IBC. TO WIT: a) ALL COMMON ROOM DOORS (office, adjunct office, laundry, and "classrooms") SHALL HAVE LEVER HANDLE HARDWARE THAT UNLOCKS FROM THE EGRESS SIDE WHEN THE HANDLE IS TURNED, AND SHALL REQUIRE NO MORE THAN 5lbs OF FORCE TO OPEN. b) LANDINGS LEVEL WITH THE INTERIOR FLOOR SHALL BE REQUIRED AT THE EXTERIOR OF THE LAUNDRY, OFFICE AND 1ST FLOOR CLASSROOM. THRESHOLDS SHALL NOT EXCEED 3/4" IN HEIGHT. c) AN ACCESSIBLE PARKING SPACE SHALL BE REQUIRED, WITH AN ACCESS AISLE IN THE SOUTH-WEST PARKING LOT. ALSO 1) LABEL THE SPACE MARKED "OFFICE" ON PLANS AS ADJUNCT OFFICE AS IT HAS NO PLUMBING FACILITIES. 2) LABEL APT. 8 MARKED ON PLANS AS "OFFICE". THIS WAY YOU WILL NOT NEED TO PROVIDE A NEW RESTROOM FOR #1 ABOVE. 3) POST A 12" ADDRESS DISPLAY PER PIMA COUNTY ZONING ORDINANCE. 4) CAP UNUSED DRAIN IN THE LAUNDRY. 5) DO NOT STORE ITEMS NEXT TO OR IMMEDIATLY ON TOP OF WATER HEATER IN STORE ROOM. 6) LABEL ALL ELECTRIC CIRCUITS IN ALL SERVICE PANELS, INCLUDING STORE ROOM. 7) ANTI-TIP DEVICES WILL BE REQUIRED ON ALL STOVES. 8) FINISH REPAIRING ALL HOLES IN CEILINGS AND WALLS BEFORE UNITS ARE OCCUPIED. 9) CAULK ALL TOILETS AT FLOOR AND ALL LAVATORIES & SINKS AT THE COUNTER AND WALL. |