Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR04763
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Test all emergency lighting units located in the building and repair or replace all defective units. |
|
12/18/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____1.The exit sign located by the East exit door shall be fully illuminated. |