Case: T08FR04759

Parcel: 10819019H


Addresses:

715 E WETMORE RD

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
12/18/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated.

_____1.The EXIT sign located above the main entrance/EXIT door shall be illuminated.

_____2.The EXIT sign located by the registers shall be fully illuminated.

_____3.The EXIT sign located by the ordering area shall be illuminated.

_____4.The EXIT sign located above the kitchen EXIT door shall be illuminated.
12/18/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system.

_____1.Test all emergency lighting units located in the building and repair or replace all defective units.