Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/18/2008

Applicant:

GOLDEN SOUTHWEST FINANCIAL GROUP LTD

Description:

Full Fire Prevention Inspection. Alejanrina Rivera 293-0088

Outstanding Inspections

Case Number: T08FR04759
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/18/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____1.Post a durable permanent sign on the outside of the sprinkler system riser room door stating " RISER ROOM".
12/18/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1.An approved cover shall be place over all open spaces in the electrical service panels located in the kitchen. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
12/18/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1.Replace the missing ceiling tile in the cleaning supply storage closet located in the kitchen.
12/18/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____1.The EXIT sign located above the main entrance/EXIT door shall be illuminated. _____2.The EXIT sign located by the registers shall be fully illuminated. _____3.The EXIT sign located by the ordering area shall be illuminated. _____4.The EXIT sign located above the kitchen EXIT door shall be illuminated.
12/18/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Test all emergency lighting units located in the building and repair or replace all defective units.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04759
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/18/2008 INSP - FULL JBURGE Approved Please correct all noted Tucson Fire Code violations.