Case: T08FR04759
Case Details
Entered Date:
12/18/2008
Applicant:
GOLDEN SOUTHWEST FINANCIAL GROUP LTD
Description:
Full Fire Prevention Inspection. Alejanrina Rivera 293-0088
Outstanding Inspections
Case Number: T08FR04759
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____1.Post a durable permanent sign on the outside of the sprinkler system riser room door stating " RISER ROOM". |
| 12/18/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1.An approved cover shall be place over all open spaces in the electrical service panels located in the kitchen. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 12/18/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1.Replace the missing ceiling tile in the cleaning supply storage closet located in the kitchen. |
| 12/18/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____1.The EXIT sign located above the main entrance/EXIT door shall be illuminated. _____2.The EXIT sign located by the registers shall be fully illuminated. _____3.The EXIT sign located by the ordering area shall be illuminated. _____4.The EXIT sign located above the kitchen EXIT door shall be illuminated. |
| 12/18/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Test all emergency lighting units located in the building and repair or replace all defective units. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04759
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2008 | INSP - FULL | JBURGE | Approved | Please correct all noted Tucson Fire Code violations. |