Case: T08FR04748

Parcel: 137053110


Addresses:

5266 S 12TH AV


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR04748

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
12/17/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
12/17/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
____ Inspection reports for griddle's extinguishing system located in the back of the building shall be provided.

____ Griddle located in back shall have an approved extinguishing system installed.
12/17/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.