Inspection History: VIOL - MOTOR FUEL DISPENSING

Date Description Inspector Results Comments
01/20/2009 VIOL - MOTOR FUEL DISPENSING Approved Spill bucket fixed
01/05/2009 VIOL - MOTOR FUEL DISPENSING Continued All corrected except 2206.6.2.6
12/11/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

" Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.
12/11/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times.

" Replace the cracked 87 octane hose on number 2 pump. There are a couple others that need to be monitored.
12/11/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet (22 860 mm) from pumps, dispensers or storage tank fill-pipe openings.

" The fire extinguisher in the auto shop needs servicing and the annual inspection. It also needs to be mounted at least 4 inches off the ground. Install an additional fire extinguisher in the market area.
12/11/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

" Provide documentation of this inspection.
12/11/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2206.6.2.6 Spill containers. A spill container having a capacity of not less than 5 gallons (19 L) shall be provided for each fill connection. For tanks with a top fill connection, spill containers shall be noncombustible and shall be fixed to the tank and equipped with a manual drain valve that drains into the primary tank.

" Repair the spill bucket. (under the blue lid)