Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2009 | VIOL - MEANS OF EGRESS | Approved | Back up power sources were replaced. Light and sign function correctly | |
| 12/11/2008 | VIOL - MEANS OF EGRESS | Correction Required | 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. " Repair the exit sign and emergency light; both must have operational back up power. |