Case: T08FR04697

Parcel: 10408005D


Addresses:

4695 N ORACLE RD

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
12/11/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes.

_____1.The open J-Box located in the communications closet shall have an approved cover.
12/11/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.

_____1.Remove the extension cord used in the southwest corner office.
NOTE: Replace it with a fused power strip.

_____2.Remove the extension cords used in the front office area.
NOTE: Replace them with fused power strips.



________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)

Full inspection done by Inspector John E. Bieg
Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________
John E. Bieg