Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/11/2008

Applicant:

4695 NORTH ORACLE GROUP LLC

Description:

Full Fire Prevention Inspection. Elliot Mayfield 888-8108

Outstanding Inspections

Case Number: T08FR04697
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
12/11/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove the extension cord used in the southwest corner office. NOTE: Replace it with a fused power strip. _____2.Remove the extension cords used in the front office area. NOTE: Replace them with fused power strips. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
12/11/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1.The open J-Box located in the communications closet shall have an approved cover.
12/11/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1.Service and tag all portable fire extinguishers.
12/11/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1.The exit signs shall be internally illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04697
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/11/2008 INSP - FULL JBURGE Approved Please correct all noted Tucson Fire Code violations.