Case: T08FR04661

Parcel: 12705063A


Addresses:

4818 E SPEEDWAY BL

Inspection Status: Correction Required

Inspection History: INSP - NIGHT

Date Description Inspector Results Comments
06/16/2009 INSP - NIGHT Correction Required DURING THE SPRINKLER DEFICIENCIES INSPECTION THE FOLLOWING ITEMS WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS.

1) UNDER REAR EXTERIOR OF DECK - REPLACE ALL PAINTED SPRINKLER HEADS

2) WEST WAREHOUSE, TENT LAUNDRY - PROVIDE SPRINKLER PROTECTION TO THE UNDER SIDE OF THE OVERHEAD DOOR

3) WEST WAREHOUSE - REPAIR THE ELECTRICAL COMNNECTION TO THE MACHINERY AS PER OUR CONVERSATION

4) WEST WAREHOUSE - PROVIDE A COVER FOR THE CEILING ELECTEICAL OUTLET

5) HAVE THE SPRINKLER CONTRACTOR REPIPE THE INSPECTORS TEST DRAIN SO THAT IT DOES NOT PUT WATER ON THE ELECTRICAL BOXES. UNABLE TO FIND DURING THIS INSPECTION.

6) NUMEROUS EXTENTION CORDS WERE IN USE. EXTENTION CORDS SHALL NOT BE USED IN PLACE OF PERMANENT WIRING, RUN THROUGH WALLS OR EXPOSED TO THE ELEMENTS.

7) A MINIMUM OF 18" SHALL BE MAINTAINED BETWEEN STOCK AND A SPRINKLER DEFLECTOR

8) THE CEILING IN THE UPPER WAREHOUSE SHALL BE REPLACED

9) HAZARDS TO FIREFIGHTERS - THE RAILING ON THE EXTERIOR BALCONY, REAR OF THE BUILDING, SHALL BE REINSTATED FOR SAFETY PURPOSES.
02/13/2009 INSP - NIGHT Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 12-8-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 4818/4826 E. SPEEDWAY. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
12/08/2008 INSP - NIGHT Correction Required DURING THE ANNUAL SPEINKLER INSPECTION, SEPT. 30, 2008, THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) CANTERA CREATIONS, REAR STORE ROOM - REMOVE THE ELECTRICAL CORD AND ELECTRICAL BOX FROM THE SPRINKLER PIPING

2) S/W WAREHOUSE-PARTY RENTALS - REMOVE THE LIGHT THAT IS WIRED TO THE SPRINKLER PIPING

3) REAR EXTERIOR - BY STEPS - REMOVE THE PLUMBING DRAIN FROM THE SPRINKLER PIPING

4) REAR EXTERIOR - UNDER DECK - REPLACE THE 5 PAINTED SPRINKLER HEADS

5) SECOND FLOOR STORE ROOM - RENTED BY PARTY RENTALS - REPAIR THE CEILING THAT IS OBSTRUCTING SPRINKLER OPERATION

6) WEST WAREHOUSE - TENT LAUNDRY - PROVIDE SPRINKLER COVERAGE TO THE OVERHEAD DOOR.

7) PARTY RENTAL - THE INSPECTORS TEST VALVE SHALL BE ACCESSABLE AND FREE FROM STORAGE

8) THE EXISTING INSPECTORS TEST DRAIN SHALL BE REPIPED SO THAT IT DOES NOT PUT WATER ON ELECTRICAL SERVICE BOXES.