SPRINKLER INSPECTION

Outstanding Inspections

Case Number: T08FR04661
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/08/2008 INSP - NIGHT EDESCHAI Correction Required DURING THE ANNUAL SPEINKLER INSPECTION, SEPT. 30, 2008, THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) CANTERA CREATIONS, REAR STORE ROOM - REMOVE THE ELECTRICAL CORD AND ELECTRICAL BOX FROM THE SPRINKLER PIPING 2) S/W WAREHOUSE-PARTY RENTALS - REMOVE THE LIGHT THAT IS WIRED TO THE SPRINKLER PIPING 3) REAR EXTERIOR - BY STEPS - REMOVE THE PLUMBING DRAIN FROM THE SPRINKLER PIPING 4) REAR EXTERIOR - UNDER DECK - REPLACE THE 5 PAINTED SPRINKLER HEADS 5) SECOND FLOOR STORE ROOM - RENTED BY PARTY RENTALS - REPAIR THE CEILING THAT IS OBSTRUCTING SPRINKLER OPERATION 6) WEST WAREHOUSE - TENT LAUNDRY - PROVIDE SPRINKLER COVERAGE TO THE OVERHEAD DOOR. 7) PARTY RENTAL - THE INSPECTORS TEST VALVE SHALL BE ACCESSABLE AND FREE FROM STORAGE 8) THE EXISTING INSPECTORS TEST DRAIN SHALL BE REPIPED SO THAT IT DOES NOT PUT WATER ON ELECTRICAL SERVICE BOXES.