Case: T08FR04440

Parcel: 13327001C


Addresses:

7980 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T08FR04440

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
10/23/2008 VIOL - MOTOR FUEL DISPENSING Approved Report recieved
10/16/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

· Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.
10/16/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.2 Emergency shutoff valves. Automatic emergency valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

· Please provide test documentation of the shear valve linkage.