Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR04414
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Buildings #1, #5, #7, #8, #9, #10, #12, #13, #16, #18, #24, and #25 The spare head box needs a head wrench For Central 2000 LF and GB sprinkler heads. | |
11/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Building #18 - Sprinkler head in riser room apperas to have plaster on it. | |
11/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Appartment 20102 - The washer/dryer closet has a sprinkler head with plaster on it. | |
11/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Bldg #22 Unit #22205 - The sprinkler head at top of the stairs has been replaced with a sidewall sprinkler head on the ceiling in place of a pendant head. | |
11/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | the spare head boxes need additional spare sprinkler heads as follows: All buildings - 2 upright heads Bldg #5 - 2 sidewall heads. Bldg #7 - 1 sidewall head. Bldg #10 - 2 sidewall and 2 pendant heads. Bldg #15 - 1 pendant head. Bldg #16 - 2 pendant heads. Bldg #18 - 2 pendant heads. Bldg #20 - 2 pendant heads. Bldg #24 - 2 pendant heads. |
|
11/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | A copy of the deficiency report is attached, a reinspection will be done 12-08-08 |