Description:

Starr Pass report of inspection

Outstanding Inspections

Case Number: T08FR04414
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
11/24/2008 INSP - LIFE SAFETY JLOYA Violation Correct the following deficiencies found on June 27 2008 as reported by Kazal fire protection.
11/24/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation A copy of the deficiency report is attached, a reinspection will be done 12-08-08
11/24/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation Appartment 20102 - The washer/dryer closet has a sprinkler head with plaster on it.
11/24/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation Bldg #22 Unit #22205 - The sprinkler head at top of the stairs has been replaced with a sidewall sprinkler head on the ceiling in place of a pendant head.
11/24/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation Building #18 - Sprinkler head in riser room apperas to have plaster on it.
11/24/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation Buildings #1, #5, #7, #8, #9, #10, #12, #13, #16, #18, #24, and #25 The spare head box needs a head wrench For Central 2000 LF and GB sprinkler heads.
11/24/2008 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation the spare head boxes need additional spare sprinkler heads as follows: All buildings - 2 upright heads Bldg #5 - 2 sidewall heads. Bldg #7 - 1 sidewall head. Bldg #10 - 2 sidewall and 2 pendant heads. Bldg #15 - 1 pendant head. Bldg #16 - 2 pendant heads. Bldg #18 - 2 pendant heads. Bldg #20 - 2 pendant heads. Bldg #24 - 2 pendant heads.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04414
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/12/2009 INSP - REINSPECTION JLOYA Approved All violations abated.