Case: T08FR04254

Parcel: 117200270


Addresses:

260 S CHURCH AV


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR04254

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
11/07/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 903.5 Testing and maintenance.
Sprinkler systems shall be tested and maintained.

Deficiencies per report # 088245 (attached)

*Head replacement and water gong repair to be done w/in 2 weeks.
*All other items to be completed w/in 30 days.

1. Replace any sprinkler which has been painted (40-50)

2. Repair water gongs @ zones 23, 24 & 35

3. Replace all noted Omega heads (recalled) in lobby and exterior canopy (51)

4. Proper # and type of spare heads to be located in box, on site, w/ required wrenches.

5. Repair/replace escutcheons