Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/07/2008

Applicant:

CITY OF TUCSON

Description:

Fire Sprinkler Inspection Issues

Outstanding Inspections

Case Number: T08FR04254
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
11/07/2008 INSP - FULL GDAURIA Correction Required Sprinkler system deficiencies per Kazal report #088245 dated 5/28/08
11/07/2008 VIOL - FIRE PROTECTION SYSTEMS GDAURIA Violation 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained. Deficiencies per report # 088245 (attached) *Head replacement and water gong repair to be done w/in 2 weeks. *All other items to be completed w/in 30 days. 1. Replace any sprinkler which has been painted (40-50) 2. Repair water gongs @ zones 23, 24 & 35 3. Replace all noted Omega heads (recalled) in lobby and exterior canopy (51) 4. Proper # and type of spare heads to be located in box, on site, w/ required wrenches. 5. Repair/replace escutcheons