Case: T08FR04209

Parcel: 10509550A


Addresses:

4821 N STONE AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04209

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2009 INSP - FULL Approved APPROVED AS PER SYSTEMS
11/05/2008 INSP - FULL Correction Required DURING THE LAST FIRE SPRINKLER INSPECTION THAT THIS OFFICE HAS RECEIVED A COPY OF , AUG., 31, 2008, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS

1) A READABLE HYDRAULIC CALCULATION PLATE SHALL BE AT THE SPRINKLER RISER

2) THE 2" MAIN DRAIN IS LEAKING AND THE VALVE DOES N OT FULLY CLOSE

3) A KEY SHALL BE AVAILABLE TO UNLOCK THE RISER VALVE AND TAMPER SWITCH, TO CORRECTLY TEST VALVES