Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

11/05/2008

Applicant:

CENTRO NP HOLDINGS 1 SPE LLC

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04209
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/05/2008 INSP - FULL EDESCHAI Approved DURING THE LAST FIRE SPRINKLER INSPECTION THAT THIS OFFICE HAS RECEIVED A COPY OF , AUG., 31, 2008, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS 1) A READABLE HYDRAULIC CALCULATION PLATE SHALL BE AT THE SPRINKLER RISER 2) THE 2" MAIN DRAIN IS LEAKING AND THE VALVE DOES N OT FULLY CLOSE 3) A KEY SHALL BE AVAILABLE TO UNLOCK THE RISER VALVE AND TAMPER SWITCH, TO CORRECTLY TEST VALVES