Case: T08FR04176

Parcel: 117120210


Addresses:

63 E CONGRESS ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
04/23/2009 INSP - FULL Approved ALL REPAIRS DONE BY KAZAL, NEW REPORT SHOW NO DEFICIENCIES.

PRE-CITATION DELEATED
04/10/2009 INSP - FULL Correction Required PRECITATION SENT 4-9-09
02/03/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-4-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 63 E. CONGRESS. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
11/04/2008 INSP - FULL Correction Required DURING THE LAST ANNUAL SPRINKLER INSPECTION REPORT THAT WAS PROVIDED THE FIRE PREVENTION, DATED 12/18/06, THE FOLLOWIND DEFICIENCIES WERE FOUND. IF THEY HAVE BEEN CORRECTED PLEASE FORWARD A COPY OF THE REPAIR MANIFEST. IF NOT THEY SHALL BE CORRECTED WITH IN 30 DAYS, WITH A COPY OF THAT REPAIR ORDER FORWARDED.

1) THERE ARE 2 SPRINKLERS ON THE MAIN FLOOR, S/W CORNER THAT ARE OBSTRUCTED BY A BEAM

2) MAIN FLOOR, N/W CORNER THERE IS A ROOM WITH A SPRINKLER HEAD AGAINST A WALL

3) OLD BASEMENT KITCHEN - WITH PART OF THE CEILING REMOVED SPRINKLERS EXCEED THE ALLOWABLE DISTANCE FROM THE DECK ABOVE

4) AN AREA BY THE N/E BASEMENT ENTRY HAS NO SPRINKLER COVERAGE

5) THE HIGH CEILING ABOVE THE DELIVERY CHUTE MAY NOT BE SPRINKLERED

6) A ROW OF SPRINKLERS ON THE MAIN FLOOR N/E EXCEED THE ALLOWABLE DISTANCE FRON THE WALL. MAXIMUM DISTANCE CAN BE 7' 6"

7) IF THE CONTROL VALVE IS NOT IN A SECURE AREA IT SHALL HAVE A LOCK AND CHAIN

8) DUCT WORK IS OBSTRUCTING ACCESS TO THE ALARM VALVE INTERIOR

9) REPLACE THE MISSING GASKET FOR THE FIRE DEPT. CONNECTION

10) REPLACE THE PAINTED SPRINKLER HEADS, 1 AT THE BOTTOM OF S/W STAIRS, AND 1 BY THE DELIVERY CHUTE