Case: T08FR04176
Case Details
Entered Date:
11/04/2008
Applicant:
SIXTY THREE BUILDING LLC
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04176
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2008 | INSP - FULL | EDESCHAI | Approved | DURING THE LAST ANNUAL SPRINKLER INSPECTION REPORT THAT WAS PROVIDED THE FIRE PREVENTION, DATED 12/18/06, THE FOLLOWIND DEFICIENCIES WERE FOUND. IF THEY HAVE BEEN CORRECTED PLEASE FORWARD A COPY OF THE REPAIR MANIFEST. IF NOT THEY SHALL BE CORRECTED WITH IN 30 DAYS, WITH A COPY OF THAT REPAIR ORDER FORWARDED. 1) THERE ARE 2 SPRINKLERS ON THE MAIN FLOOR, S/W CORNER THAT ARE OBSTRUCTED BY A BEAM 2) MAIN FLOOR, N/W CORNER THERE IS A ROOM WITH A SPRINKLER HEAD AGAINST A WALL 3) OLD BASEMENT KITCHEN - WITH PART OF THE CEILING REMOVED SPRINKLERS EXCEED THE ALLOWABLE DISTANCE FROM THE DECK ABOVE 4) AN AREA BY THE N/E BASEMENT ENTRY HAS NO SPRINKLER COVERAGE 5) THE HIGH CEILING ABOVE THE DELIVERY CHUTE MAY NOT BE SPRINKLERED 6) A ROW OF SPRINKLERS ON THE MAIN FLOOR N/E EXCEED THE ALLOWABLE DISTANCE FRON THE WALL. MAXIMUM DISTANCE CAN BE 7' 6" 7) IF THE CONTROL VALVE IS NOT IN A SECURE AREA IT SHALL HAVE A LOCK AND CHAIN 8) DUCT WORK IS OBSTRUCTING ACCESS TO THE ALARM VALVE INTERIOR 9) REPLACE THE MISSING GASKET FOR THE FIRE DEPT. CONNECTION 10) REPLACE THE PAINTED SPRINKLER HEADS, 1 AT THE BOTTOM OF S/W STAIRS, AND 1 BY THE DELIVERY CHUTE |