Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04159
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2009 | INSP - FULL | Approved | APPROVED EXCEPT FOR CALC. PLATE. WILL FIELD CHECK WHEN INSTALLED | |
04/10/2009 | INSP - FULL | Correction Required | PRECITATION SENT 4-8-09 | |
02/13/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-4-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING TEH FIRE PROTECTION SYSTEM AT 52/58 W. CONGRESS. IF CORRECTED HAVE THE CONTRACTOR OR RECORD FORWARD THEIR REPORT. |
|
11/04/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFESTSHALL BE FORWARDED TO THIS OFFICE. 1) PROVIDE A HYDRAULIC CALCULATION PLATE FOR RISER # 2 2) PROVIDE CAPS FOR THE FIRE DEPARTMENT CONNECTION 3) THE SPARE HEAD BOS SHALL HAVE A FULL COMPLIMENT OF HEADS, PROVIDE 2 VERTICLE SIDEWALLS, 2 HORIZONTAL SIDEWALLS, 2 STANDARD PENDANT HEADS AND 2 QUICK RESPONSE STANDARD PENDANT HEADS. 3) IN THE BASEMENT THERE ARE 3 SPRINKLER HEADS THAT MAY BE OBSTRUCTED BY LIGHTS 4) BASEMENT STORE ROOM # 3, A SPRINKLER HEAD EXCEEDS THE ALLOWABLE DISTANCE FROM A WALL. REINSTATE A SPRINKLER HEAD AT THE PLUGGED OFF OUTLET. 5) THE GROUND FLOOR STAIRS AT # 52, LEADING TO THE BASEMENT IS LACKING SPRINKLER COVERAGE. PROVIDE COVERAGE. 6) SPRINKLERS THAT ARE 50 YEARS OLD SHALL EITHER HAVE A TESTED SAMPLE OR THEY SHALL BE CHANGED OUT. 7) IF THE CONTROL VALVE IS NOT IN A SECURE LOCATION IT SHALL HAVE A LOCK AND CHAIN 8) THE INSPECTORS TEST VALVE FOR SYSTEM # 2 SHALL BE LOCATED. |