Case: T08FR04159

Parcel: 117120470


Addresses:

52 W CONGRESS ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/15/2009 INSP - FULL Approved APPROVED EXCEPT FOR CALC. PLATE. WILL FIELD CHECK WHEN INSTALLED
04/10/2009 INSP - FULL Correction Required PRECITATION SENT 4-8-09
02/13/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-4-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING TEH FIRE PROTECTION SYSTEM AT 52/58 W. CONGRESS. IF CORRECTED HAVE THE CONTRACTOR OR RECORD FORWARD THEIR REPORT.
11/04/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFESTSHALL BE FORWARDED TO THIS OFFICE.

1) PROVIDE A HYDRAULIC CALCULATION PLATE FOR RISER # 2

2) PROVIDE CAPS FOR THE FIRE DEPARTMENT CONNECTION

3) THE SPARE HEAD BOS SHALL HAVE A FULL COMPLIMENT OF HEADS, PROVIDE 2 VERTICLE SIDEWALLS, 2 HORIZONTAL SIDEWALLS, 2 STANDARD PENDANT HEADS AND 2 QUICK RESPONSE STANDARD PENDANT HEADS.

3) IN THE BASEMENT THERE ARE 3 SPRINKLER HEADS THAT MAY BE OBSTRUCTED BY LIGHTS

4) BASEMENT STORE ROOM # 3, A SPRINKLER HEAD EXCEEDS THE ALLOWABLE DISTANCE FROM A WALL. REINSTATE A SPRINKLER HEAD AT THE PLUGGED OFF OUTLET.

5) THE GROUND FLOOR STAIRS AT # 52, LEADING TO THE BASEMENT IS LACKING SPRINKLER COVERAGE. PROVIDE COVERAGE.

6) SPRINKLERS THAT ARE 50 YEARS OLD SHALL EITHER HAVE A TESTED SAMPLE OR THEY SHALL BE CHANGED OUT.

7) IF THE CONTROL VALVE IS NOT IN A SECURE LOCATION IT SHALL HAVE A LOCK AND CHAIN

8) THE INSPECTORS TEST VALVE FOR SYSTEM # 2 SHALL BE LOCATED.