Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2009 | INSP - FULL | Approved | APPROVED AS PER INSP. SCHULTZ | |
| 02/20/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-3-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 5360 E. PIMA. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 11/03/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE SPARE HEAD BOX NEEDS 2, 155 DEGREE, BRASS, STANDARD, MODEL E, 1/2 INCH HORIZONTAL SIDEWALL SPRINKLER HEADS 2) THE FOLLOWING AREAS HAVE PAINT OVERSPRAY ON SPRINKLERS, THEY SHALL BE CHANGED OUT: 7TH/8TH.GRADE CLASSROOM CLOSET, 3 CLOSETS OFF HALLWAY. THIS IS AT THE SOUTH END OF THE HJALLWAY. 3) IF THE SPRINKLER RISER CONTROL VALVE IS NOT IN A SECURE LOCATION IT SHALL BE PROVIDED WITH A LOCK AND CHAIN |