Case: T08FR04149

Parcel: 12112402A


Addresses:

5360 E PIMA ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/27/2009 INSP - FULL Approved APPROVED AS PER INSP. SCHULTZ
02/20/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-3-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 5360 E. PIMA. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
11/03/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) THE SPARE HEAD BOX NEEDS 2, 155 DEGREE, BRASS, STANDARD, MODEL E, 1/2 INCH HORIZONTAL SIDEWALL SPRINKLER HEADS

2) THE FOLLOWING AREAS HAVE PAINT OVERSPRAY ON SPRINKLERS, THEY SHALL BE CHANGED OUT: 7TH/8TH.GRADE CLASSROOM CLOSET, 3 CLOSETS OFF HALLWAY. THIS IS AT THE SOUTH END OF THE HJALLWAY.

3) IF THE SPRINKLER RISER CONTROL VALVE IS NOT IN A SECURE LOCATION IT SHALL BE PROVIDED WITH A LOCK AND CHAIN