Case: T08FR04149
Case Details
Entered Date:
11/03/2008
Applicant:
STREAMS IN DESERT EVANGELICAL LUTHERAN
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04149
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2008 | INSP - FULL | EDESCHAI | Approved | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE SPARE HEAD BOX NEEDS 2, 155 DEGREE, BRASS, STANDARD, MODEL E, 1/2 INCH HORIZONTAL SIDEWALL SPRINKLER HEADS 2) THE FOLLOWING AREAS HAVE PAINT OVERSPRAY ON SPRINKLERS, THEY SHALL BE CHANGED OUT: 7TH/8TH.GRADE CLASSROOM CLOSET, 3 CLOSETS OFF HALLWAY. THIS IS AT THE SOUTH END OF THE HJALLWAY. 3) IF THE SPRINKLER RISER CONTROL VALVE IS NOT IN A SECURE LOCATION IT SHALL BE PROVIDED WITH A LOCK AND CHAIN |