Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

11/03/2008

Applicant:

STREAMS IN DESERT EVANGELICAL LUTHERAN

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR04149
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/03/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE SPARE HEAD BOX NEEDS 2, 155 DEGREE, BRASS, STANDARD, MODEL E, 1/2 INCH HORIZONTAL SIDEWALL SPRINKLER HEADS 2) THE FOLLOWING AREAS HAVE PAINT OVERSPRAY ON SPRINKLERS, THEY SHALL BE CHANGED OUT: 7TH/8TH.GRADE CLASSROOM CLOSET, 3 CLOSETS OFF HALLWAY. THIS IS AT THE SOUTH END OF THE HJALLWAY. 3) IF THE SPRINKLER RISER CONTROL VALVE IS NOT IN A SECURE LOCATION IT SHALL BE PROVIDED WITH A LOCK AND CHAIN