Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2009 | INSP - FULL | Approved | PRE-CITATION DELEATED, CORRECTIONS MADE | |
| 04/10/2009 | INSP - FULL | Correction Required | PRECITATION SENT 4-8-09 | |
| 01/30/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-03-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 2430 N. FLOWING WELLS RD. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 11/03/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL INSPECTION OF THE FIRE SPRINKLER SYSTEM THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE FIRE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL INSPECTION 2) THE SUPPLY LINE BELOW THE CONTROL VALVE IS CORRODED, IF NECESSARY REPLACE 3) THE SPARE HEAD BOX SHALL BE AT THE RISER FOR ACCESSABILITY 4) IT IS RECOMMENDED TO HAVE THE FLOW SWITCH TIED INTO THE SECURITY MONITERING SYSTEM. |