Case: T08FR04127
Case Details
Entered Date:
11/03/2008
Applicant:
USTARIZ GERMAN
Description:
SPRINKLER INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04127
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2008 | INSP - FULL | EDESCHAI | Approved | DURING THE ANNUAL INSPECTION OF THE FIRE SPRINKLER SYSTEM THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE FIRE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL INSPECTION 2) THE SUPPLY LINE BELOW THE CONTROL VALVE IS CORRODED, IF NECESSARY REPLACE 3) THE SPARE HEAD BOX SHALL BE AT THE RISER FOR ACCESSABILITY 4) IT IS RECOMMENDED TO HAVE THE FLOW SWITCH TIED INTO THE SECURITY MONITERING SYSTEM. |