Case: T08FR04060

Parcel: 138111740


Addresses:

6121 S 6TH AV

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/30/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.
_____ Clear area around electrical panels and transformer.
10/30/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident.
***Provide such signage.
10/30/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4.1 - Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363.
10/30/2008 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.