Case: T08FR04060
Case Details
Entered Date:
10/30/2008
Applicant:
KAY FAMILY LLP
Description:
LIQUOR DAN FULL INSPECTION
Outstanding Inspections
Case Number: T08FR04060
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 10/30/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ***Provide such signage. |
| 10/30/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer. |
| 10/30/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.4.1 - Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. |
| 10/30/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
| 10/30/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 906.5 - Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. |
| 10/30/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. |
| 10/30/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. |
| 10/30/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | TFC 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be iminished along the path of egress travel. _____ Clear exit path, and maintain it this way. |
| 10/30/2008 | VIOL - MEANS OF EGRESS | JLOYA | Violation | TFC 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR04060
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2008 | INSP - REINSPECTION | JLOYA | Approved | 2nd reinspection done with all violations abated. |