Case: T08FR04032

Parcel: 106070380


Addresses:

1010 W LIND ST

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
10/29/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.3.5 Security grilles. In Groups B, F, M and S,
horizontal sliding or vertical security grilles are permitted
at the main exit and shall be openable from the inside
without the use of a key or special knowledge or effort
during periods that the space is occupied. The grilles
shall remain secured in the full-open position during the
period of occupancy by the general public.

_____1. The security grills shall be locked in the open position when the buildings are occupied.
10/29/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated.

_____1. The exit sign located above the west exit door located in the gym shall be illuminated and shall have emergency back-up power.

_____2. The exit sign located above the east exit door located in the gym shall be illuminated and shall have emergency back-up power.

_____3. The exit sign located located in the MPR shall be illuminated and shall have emergency back-up power.

_____4. The exit signs located located in the MPR east shall be illuminated and shall have emergency back-up power.
10/29/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system.

_____1. Repair the broken emergency lighting unit located in the activity room.