Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

10/29/2008

Applicant:

CITY OF TUCSON

Description:

Full Fire Prevention Inspection. Berlin Loa 888-7716

Outstanding Inspections

Case Number: T08FR04032
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
10/29/2008 INSP - FULL JBURGE Correction Required Please correct all noted Tucson Fire Code violations:
10/29/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. _____1. Remove the BBQ and propane tanks from the storage closet located in MPR.
10/29/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. _____1. Remove the storage from the water heater closet located in the office copy room. _____2. Remove the storage from the water heater closet located in the MPR.
10/29/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Address numbers. (cot mod) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. _____1.Comply with Pima County address display requirements. NOTE: the numbers can't be painted on.
10/29/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove the extension cord used to power the frige located in the south building snack room. NOTE: Repalce it with a fused power strip. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
10/29/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Service and test the fire alarm system and provide documentation of such work. _____2.Service and test the automatic sprinkler system located in the gym and provide documentation of such work.
10/29/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.3.5 Security grilles. In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. _____1. The security grills shall be locked in the open position when the buildings are occupied.
10/29/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____1. The exit sign located above the west exit door located in the gym shall be illuminated and shall have emergency back-up power. _____2. The exit sign located above the east exit door located in the gym shall be illuminated and shall have emergency back-up power. _____3. The exit sign located located in the MPR shall be illuminated and shall have emergency back-up power. _____4. The exit signs located located in the MPR east shall be illuminated and shall have emergency back-up power.
10/29/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair the broken emergency lighting unit located in the activity room.