Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2009 | INSP - FULL | Approved | REPAIR REPORT SENT TO SYSTEMS | |
| 02/04/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 12-10-2008, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 6602 E. GRANT. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 12/10/2008 | INSP - FULL | Approved | ||
| 12/10/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE WATER FLOW INDICATION, ELECTRICAL BELL, WAS NOT FUNCTIONAL AND SHALL BE REPAIRED 2) THE SPARE HEAD BOX REQUIRES A SPECIAL WRENCH FOR CHANGING OUT SPRINKLER HEADS 3) THE SPRINKLER RISER CHECK VALVE IS NOT SEATING PROPERLY AND SHALL BE REPAIRED OR REPLACED |
|
| 10/24/2008 | INSP - FULL | Correction Required | FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS. WHEREAS THIS OFFICE DOES NOT HAVE A CURRENT RECORD OF INSPECTION, A COPY SHALL BE PROVIDED THE FIRE PREVENTION OFFICE WITH IN 30 DAYS |