Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T08FR03927

Parcel: 13316020Q


Addresses:

6602 E GRANT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
04/22/2009 INSP - FULL Approved REPAIR REPORT SENT TO SYSTEMS
02/04/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 12-10-2008, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 6602 E. GRANT. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
12/10/2008 INSP - FULL Approved
12/10/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) THE WATER FLOW INDICATION, ELECTRICAL BELL, WAS NOT FUNCTIONAL AND SHALL BE REPAIRED

2) THE SPARE HEAD BOX REQUIRES A SPECIAL WRENCH FOR CHANGING OUT SPRINKLER HEADS

3) THE SPRINKLER RISER CHECK VALVE IS NOT SEATING PROPERLY AND SHALL BE REPAIRED OR REPLACED
10/24/2008 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS. WHEREAS THIS OFFICE DOES NOT HAVE A CURRENT RECORD OF INSPECTION, A COPY SHALL BE PROVIDED THE FIRE PREVENTION OFFICE WITH IN 30 DAYS