SPRINKLER INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03927
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/10/2008 INSP - FULL EDESCHAI Approved DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE WATER FLOW INDICATION, ELECTRICAL BELL, WAS NOT FUNCTIONAL AND SHALL BE REPAIRED 2) THE SPARE HEAD BOX REQUIRES A SPECIAL WRENCH FOR CHANGING OUT SPRINKLER HEADS 3) THE SPRINKLER RISER CHECK VALVE IS NOT SEATING PROPERLY AND SHALL BE REPAIRED OR REPLACED