Case: T08FR03228

Parcel: 11712033A


Addresses:

1 W CONGRESS ST


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR03228

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/29/2008 VIOL - MEANS OF EGRESS Correction Required 1011.5.3 Power source.
Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code

_____ Fix, repair, and/or replace all exit signs in order to meet code standards

1027.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027.

_____ Fix, repair, and/or replace the emergency lighting in order to meet code standards