Case: T08FR03084

Parcel: 12402034D


Addresses:

1701 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
05/04/2009 VIOL - FIRE PROTECTION SYSTEMS Approved
09/24/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Continue Fire Watch duties until Fire Alarm is repaired.
09/24/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.4 Extinguishing system service. Automatic
fire-extinguishing systems shall be serviced at least
every 6 months and after activation of the system.
Inspection shall be by qualified individuals, and a certificate
of inspection shall be forwarded to the fire code official
upon completion.

____Commercial cooking extinguishing system is due for 6 month service/inspection.
09/24/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 903.2.7 Group R.
Existing sorority and fraternity house and exiting Group R-4 occupancies shall have automatic sprinkler systems installed. A permit shall be issued within two years of the adoption of this code and the work shall be completed within three years of the adoption of this code.

____This ordinance took effect on October 23, 2007 and requires completion by October 22, 2010.