Case: T08FR03084
Case Details
Entered Date:
09/24/2008
Applicant:
TUCSON DELTA CHI ALUMNI BOARD
Description:
FULL FIRE INSPECTION.
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR03084
Case Description: INSPECTION
Total Completed Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Approved | TFC 903.2.7 Group R. Existing sorority and fraternity house and exiting Group R-4 occupancies shall have automatic sprinkler systems installed. A permit shall be issued within two years of the adoption of this code and the work shall be completed within three years of the adoption of this code. ____This ordinance took effect on October 23, 2007 and requires completion by October 22, 2010. |
| 09/24/2008 | VIOL - COMPRESSED GASES | JVINCENT | Approved | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. ____Secure CO2 tanks used for fountain drinks. |
| 09/24/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Approved | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system... ____Repair all damaged or inoperable emergency lighting units: ____Light over trophy case. ____Light near boiler room. ____Light near chapter room. ____Light in East stairwell. ____Light in West stairwell. ____Light near House Managers office. ____Lights near rooms: ____16 ____233 ____01 ____000 ____122 |
| 09/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Approved | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ____Commercial cooking extinguishing system is due for 6 month service/inspection. |
| 09/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Approved | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Continue Fire Watch duties until Fire Alarm is repaired. |
| 09/24/2008 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Approved | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ____Coverplate needed for exposed electrical near main/front door. |
| 09/24/2008 | VIOL - EMERGENCY PLAN/PREPARE | JVINCENT | Approved | 405.2 Frequency. Required emergency evacuation drills shall be held at the intervals specified in Table 405.2 or more frequently where necessary to familiarize all occupants with the drill procedure. ____Four Evacuation Drills required annually. Keep records on-site. |
| 09/24/2008 | INSP - FULL | JVINCENT | Approved | FULL FIRE INSPECTION. |