Description:

FULL FIRE INSPECTION.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR03084
Case Description: INSPECTION
Total Completed Inspections - 8
End Date Description Inspector Results Comments
09/24/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved TFC 903.2.7 Group R. Existing sorority and fraternity house and exiting Group R-4 occupancies shall have automatic sprinkler systems installed. A permit shall be issued within two years of the adoption of this code and the work shall be completed within three years of the adoption of this code. ____This ordinance took effect on October 23, 2007 and requires completion by October 22, 2010.
09/24/2008 VIOL - COMPRESSED GASES JVINCENT Approved 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. ____Secure CO2 tanks used for fountain drinks.
09/24/2008 VIOL - MEANS OF EGRESS JVINCENT Approved 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system... ____Repair all damaged or inoperable emergency lighting units: ____Light over trophy case. ____Light near boiler room. ____Light near chapter room. ____Light in East stairwell. ____Light in West stairwell. ____Light near House Managers office. ____Lights near rooms: ____16 ____233 ____01 ____000 ____122
09/24/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ____Commercial cooking extinguishing system is due for 6 month service/inspection.
09/24/2008 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Continue Fire Watch duties until Fire Alarm is repaired.
09/24/2008 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Approved 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ____Coverplate needed for exposed electrical near main/front door.
09/24/2008 VIOL - EMERGENCY PLAN/PREPARE JVINCENT Approved 405.2 Frequency. Required emergency evacuation drills shall be held at the intervals specified in Table 405.2 or more frequently where necessary to familiarize all occupants with the drill procedure. ____Four Evacuation Drills required annually. Keep records on-site.
09/24/2008 INSP - FULL JVINCENT Approved FULL FIRE INSPECTION.