Case: T08FR02867

Parcel: 14024058G


Addresses:

1075 E WIEDING RD

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/09/2008 INSP - FULL Violation Copy of Full sprinkler inspection report.
NFPA 9.6.2.9, Wrench and six spare heads on site at all times.
10/09/2008 INSP - FULL Violation 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor cover-ings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
605.5.1 Power supply. Extension cords shall be plugged directly
into an approved receptacle, power tap or multiplug
adapter and, except for approved multiplug extension cords,
shall serve only one portable appliance.
Do not use extension cords for perminant wiring.
10/09/2008 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Do not block electrical panels.
10/09/2008 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.
Service standpipes yearly. Send report to the Fire Prevention Center @ 797 E. Ajo Way, Tucson 85713.
09/18/2008 INSP - FULL Correction Required sprinkler test full inspection needed