Case: T08FR02867
Case Details
Entered Date:
09/18/2008
Applicant:
WIEDING ROAD LLC
Description:
sprinkler test needed
Outstanding Inspections
Case Number: T08FR02867
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2008 | INSP - FULL | JNAGORE | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Do not block electrical panels. |
| 10/09/2008 | INSP - FULL | JNAGORE | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor cover-ings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 605.5.1 Power supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance. Do not use extension cords for perminant wiring. |
| 10/09/2008 | INSP - FULL | JNAGORE | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Service standpipes yearly. Send report to the Fire Prevention Center @ 797 E. Ajo Way, Tucson 85713. |
| 10/09/2008 | INSP - FULL | JNAGORE | Violation | Copy of Full sprinkler inspection report. NFPA 9.6.2.9, Wrench and six spare heads on site at all times. |