Case: T08FR02863

Parcel: 13733913A


Addresses:

1900 W VALENCIA RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR02863

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2009 INSP - FULL Approved All deficiencies corrected.
07/14/2009 INSP - FULL Correction Required A full inspection was conducted. The following items need to be addressed and corrected by 7/28/2009:
1. No report available for the 1/09 (Fire Trol tag) fire sprinkler inspection. Provide report and maintain a copy on site for 3 years. International Fire Code (IFC) 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be
maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.
2. The electrical panels and fire sprinkler riser located in the store room are obstructed from quick and immediate access. Remove all obstrctions and maintain a 3 foot clear space around these devices. IFC 605.3. Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
09/18/2008 INSP - FULL Correction Required sprinkler test full inspection needed - complaint came in regarding the emergency exits being blocked by beer, caller states he spoke with manager and they have problems with people doing beer runs.