Case: T08FR02825

Parcel: 115045670


Addresses:

906 N 1ST AV


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR02825

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
10/09/2008 VIOL - FIRE PROTECTION SYSTEMS Approved
09/16/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.4 Extinguishing system service. Automatic
fire-extinguishing systems shall be serviced at least
every 6 months and after activation of the system.
Inspection shall be by qualified individuals, and a certificate
of inspection shall be forwarded to the fire code official
upon completion.

____Commercial cooking extinguishing system due for 6 month service/inspection.
09/16/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.5.2 Class K portable fire extinguishers.

____Install/Mount Class K in kitchen area. If already installed make sure its annual inspection is current.
09/16/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.

____Have the hood system professionally cleaned.
09/16/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Fire alarm due for an annual inspection.