Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR02825
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
09/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ____Commercial cooking extinguishing system due for 6 month service/inspection. |
|
09/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.5.2 Class K portable fire extinguishers. ____Install/Mount Class K in kitchen area. If already installed make sure its annual inspection is current. |
|
09/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ____Have the hood system professionally cleaned. |
|
09/16/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Fire alarm due for an annual inspection. |