Case: T08FR02746

Parcel: 11712033A


Addresses:

27 N STONE AV


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02746

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/10/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where
the following exists:
2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background.

_____1.Post the above wording on the inside of the entrance/exit door.
09/10/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or
other emergency when the areas served by such exits are occupied.

_____1.Remove all storage from the Fox Theatre exit access walkway located on the North and West side of your business.