Case: T08FR02742

Parcel: 11712033A


Addresses:

17 N STONE AV


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02742

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/10/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.

_____1.The exit sign located above the entrance/exit door shall be illuminated at all times.
09/10/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.3 Obstructions. A means of egress shall be free from
obstructions that would prevent its use.

_____1.Remove all storage from obstructing the means of egress located on the outside of the kitchen door.
09/10/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

_____1.Remove the locking-bar and hardware from the west kitchen door.
NOTE:Use a thumb-turn deadbolt to secure the door.