Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR02742
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1.The exit sign located above the entrance/exit door shall be illuminated at all times. |
|
09/10/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____1.Remove all storage from obstructing the means of egress located on the outside of the kitchen door. |
|
09/10/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1.Remove the locking-bar and hardware from the west kitchen door. NOTE:Use a thumb-turn deadbolt to secure the door. |