Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FLAMMABLE FINISHES
Case Number - T08FR02336
Inspection Description - VIOL - FLAMMABLE FINISHES
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2008 | VIOL - FLAMMABLE FINISHES | Correction Required | TFC 1505.3.4 Dip-tank covers. Dip-tank covers allowed by Section 1505.4.1 shall be capable of manual operation and shall be automatic closing by approved automatic-closing devices designed to operate in the event of a fire. _____1.The large dip tank located outside shall have an approved automatic closing lid designed to operate in the event of a fire. NOTE: THE SOLVENT USED IS NON-FLAMMABLE AND NON-COMBUSTIBLE. SELF CLOSING LID NOT REQUIRED. _____2.Replace the missing fuseable link for the automatic closing lid on the small solvent parts cleaner located in the cleaning room. |
|
| 08/08/2008 | VIOL - FLAMMABLE FINISHES | Correction Required | TFC 1503.2.6 Smoking prohibited. Smoking shall be prohibited in flammable vapor areas and hazardous materials storage rooms associated with flammable finish processes. “No Smoking” signs complying with Section 310 shall be conspicuously posted in such areas. _____.Post "NO SMOKING" signs around the dip tanks, flammable liquid and gas storage areas and inside the repair shops. |
|
| 08/08/2008 | VIOL - FLAMMABLE FINISHES | Correction Required | TFC 1503.2.7 Welding warning signs. Welding, cutting and similar spark-producing operations shall not be conducted in or adjacent to flammable vapor areas or dipping or coating operations unless precautions have been taken to provide safety. Conspicuous signs with the following warning shall be posted in the vicinity of flammable vapor areas, dipping operations and paint storage rooms: NO WELDING THE USE OF WELDING OR CUTTING EQUIPMENT IN OR NEAR THIS AREA IS DANGEROUS BECAUSE OF FIRE AND EXPLOSION HAZARDS. WELDING AND CUTTING SHALL BE DONE ONLY UNDER THE SUPERVISION OF THE PERSON IN CHARGE. _____1.Post the above stated sign in a conspicuous location by the Dip tank, parts cleaner and by any flammable and combustible liquid or gas storage or use area. |