Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR02336

Parcel: 11515005C


Addresses:

815 W GRANT RD


Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE FINISHES

Case Number - T08FR02336

Inspection Description - VIOL - FLAMMABLE FINISHES

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/08/2008 VIOL - FLAMMABLE FINISHES Correction Required TFC 1505.3.4 Dip-tank covers. Dip-tank covers allowed by
Section 1505.4.1 shall be capable of manual operation and
shall be automatic closing by approved automatic-closing
devices designed to operate in the event of a fire.

_____1.The large dip tank located outside shall have an approved automatic closing lid designed to operate in the event of a fire.
NOTE: THE SOLVENT USED IS NON-FLAMMABLE AND NON-COMBUSTIBLE. SELF CLOSING LID NOT REQUIRED.

_____2.Replace the missing fuseable link for the automatic closing lid on the small solvent parts cleaner located in the cleaning room.
08/08/2008 VIOL - FLAMMABLE FINISHES Correction Required TFC 1503.2.6 Smoking prohibited. Smoking shall be prohibited
in flammable vapor areas and hazardous materials storage
rooms associated with flammable finish processes. “No
Smoking” signs complying with Section 310 shall be conspicuously
posted in such areas.

_____.Post "NO SMOKING" signs around the dip tanks, flammable liquid and gas storage areas and inside the repair shops.
08/08/2008 VIOL - FLAMMABLE FINISHES Correction Required TFC 1503.2.7 Welding warning signs. Welding, cutting and
similar spark-producing operations shall not be conducted
in or adjacent to flammable vapor areas or dipping or coating
operations unless precautions have been taken to provide
safety. Conspicuous signs with the following warning
shall be posted in the vicinity of flammable vapor areas, dipping
operations and paint storage rooms:

NO WELDING
THE USE OF WELDING OR CUTTING
EQUIPMENT IN OR NEAR THIS AREA
IS DANGEROUS BECAUSE OF FIRE
AND EXPLOSION HAZARDS. WELDING
AND CUTTING SHALL BE DONE ONLY
UNDER THE SUPERVISION OF THE
PERSON IN CHARGE.

_____1.Post the above stated sign in a conspicuous location by the Dip tank, parts cleaner and by any flammable and combustible liquid or gas storage or use area.