Case: T08FR02336

Parcel: 11515005C


Addresses:

815 W GRANT RD

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
08/08/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.3 Obstructions. A means of egress shall be free from
obstructions that would prevent its use.

_____1.Remove the storage from obstructing the egress door located in the parts storage room.

_____2.The east exterior door located in the machine shop shall not be obstructed by machinery.
08/08/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

_____1.Remove the double-keyed lock from the east exterior door located in the machine shop.
NOTE:Replace the double-keyed lock with a thumb-turn lock.

_____2.Remove the double-keyed lock from the exterior door located in the southeast bay.
NOTE:Replace the double-keyed lock with a thumb-turn lock.