Case: T08FR02129

Parcel: 140221160


Addresses:

1895 E VALENCIA RD


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T08FR02129

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
08/12/2008 VIOL - MOTOR FUEL DISPENSING Approved All records of testing has been received and filed
07/24/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

ยท Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.
07/24/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet from pumps, dispensers or storage tank fill-pipe openings.