Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MOTOR FUEL DISPENSING
Case Number - T08FR02129
Inspection Description - VIOL - MOTOR FUEL DISPENSING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2008 | VIOL - MOTOR FUEL DISPENSING | Approved | All records of testing has been received and filed | |
07/24/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation. ยท Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer. |
|
07/24/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet from pumps, dispensers or storage tank fill-pipe openings. |