Case: T08FR02107

Parcel: 11005021A


Addresses:

2959 N SWAN RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR02107

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/04/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
07/24/2008 INSP - FULL Violation 1.) TFC 901.6.2 RECORDS OF SPRINKLER SYSTEM INSPECTIONS, TESTS AND MAINTENANCE SHALL BE MAINTAINED ON THE PREMISES FOR A MIN. OF 3 YEARS. PAPER WORK IS REQUIRED TO SHOW PROOF THAT THE ANNUAL SPRINKLER SYSTEM INSPECTION WAS DONE.
07/24/2008 INSP - FULL Violation 2.) TFC 3003.5.3 CO2 BOTTLES IN COOLER ROOM NEED TO BE SECURED TO PREVENT FALLING. ALSO IN THE KITCHEN AND NEAR OFFICE DOOR.
07/24/2008 INSP - FULL Violation 3.) TFC 703.1.1 CEILING TILES IN PALAMINO BUS STATION NEED TO BE PUT INTO PLACE TO PROVIDE REQUIRED FIREBLOCKING AND DRAFTSTOPPING.
07/24/2008 INSP - FULL Violation 4.) TFC 1027.8 EXIT DOOR ON THE NORTH WALL OF THE PALAMINO ROOM NEEDS TO BE REPAIRED OR SERVICED SO THAT IT OPENS WITH 15 LBS. OF FORCE OR LESS.
07/24/2008 INSP - FULL Violation 5.) TFC 1006.3 THE EMERGENCY ILLUMINATION SYSTEM FOR THE BUILDING MUST BE SHOWN TO OPERATE PROPERLY.
07/24/2008 INSP - FULL Violation 6.) TFC 605.6 TWO ELECTRICAL OUTLETS IN THE GEKUS BUS STATION NEED TO HAVE COVER PLATES INSTALLED.
07/24/2008 INSP - FULL Violation 7.) TFC 605.6 AN ELECTRICAL OUTLET IN THE KITCHEN NEAR THE SINK ON THE EAST WALL NEEDS A COVER PLATE INSTALLED.
07/24/2008 INSP - FULL Violation 8.) TFC 906.2 THE SILVER "K" TYPE EXTINGUISHER IN THE BACK KITCHEN NEEDS TO HAVE A CURRENT INSPECTION TAG.
07/24/2008 INSP - FULL Violation 9.) TFC 605.5 THE ORANGE EXTENSION CORD USED TO POWER THE SMALL REFRIGERATOR BEHIND THE BACK BAR IS NOT ALLOWED TO BE USED AS A SUBSTITUTE FOR PERMANENT WIRING.
07/24/2008 INSP - FULL Violation 10.) TFC 1028. 2 THE EXIT ACCESS FROM THE BACK BAR ROOM ONTO THE BACK PATIO MUST BE KEPT UNOBSTRUCTED. ARRANGE TABLES AND POTTED PLANTS TO PROVIDE A 3 FOOT WIDE EXIT ACCESS.
07/24/2008 INSP - FULL Violation 11.) TFC 1008.1.8.5 THE EXIT GATE FROM THE REAR PATIO NEEDS TO HAVE THE DOUBLE KEYED DEAD BOLT REPLACED WITH A THUMB TURN LATCH ON THE EGRESS SIDE.
07/24/2008 INSP - FULL Violation 12.) TFC 315.2.1 STORAGE ON TOP OF RACK IN THE MIDDLE OF THE ROOM ON THE EAST END OF THE WINE STORAGE AREA NEEDS TO BE REMOVED TO AVOID BLOCKING SPRINKLER COVERAGE.
07/24/2008 INSP - FULL Violation 13.) TFC 605.6 THE ELECTRICAL JUNCTION BOX IN THE
CEILING NEAR THE ENTRANCE TO WINE STORAGE AREA NEEDS A COVER PLATE INSTALLED.