Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR02107
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/04/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. | |
07/24/2008 | INSP - FULL | Violation | 1.) TFC 901.6.2 RECORDS OF SPRINKLER SYSTEM INSPECTIONS, TESTS AND MAINTENANCE SHALL BE MAINTAINED ON THE PREMISES FOR A MIN. OF 3 YEARS. PAPER WORK IS REQUIRED TO SHOW PROOF THAT THE ANNUAL SPRINKLER SYSTEM INSPECTION WAS DONE. | |
07/24/2008 | INSP - FULL | Violation | 2.) TFC 3003.5.3 CO2 BOTTLES IN COOLER ROOM NEED TO BE SECURED TO PREVENT FALLING. ALSO IN THE KITCHEN AND NEAR OFFICE DOOR. | |
07/24/2008 | INSP - FULL | Violation | 3.) TFC 703.1.1 CEILING TILES IN PALAMINO BUS STATION NEED TO BE PUT INTO PLACE TO PROVIDE REQUIRED FIREBLOCKING AND DRAFTSTOPPING. | |
07/24/2008 | INSP - FULL | Violation | 4.) TFC 1027.8 EXIT DOOR ON THE NORTH WALL OF THE PALAMINO ROOM NEEDS TO BE REPAIRED OR SERVICED SO THAT IT OPENS WITH 15 LBS. OF FORCE OR LESS. | |
07/24/2008 | INSP - FULL | Violation | 5.) TFC 1006.3 THE EMERGENCY ILLUMINATION SYSTEM FOR THE BUILDING MUST BE SHOWN TO OPERATE PROPERLY. | |
07/24/2008 | INSP - FULL | Violation | 6.) TFC 605.6 TWO ELECTRICAL OUTLETS IN THE GEKUS BUS STATION NEED TO HAVE COVER PLATES INSTALLED. | |
07/24/2008 | INSP - FULL | Violation | 7.) TFC 605.6 AN ELECTRICAL OUTLET IN THE KITCHEN NEAR THE SINK ON THE EAST WALL NEEDS A COVER PLATE INSTALLED. | |
07/24/2008 | INSP - FULL | Violation | 8.) TFC 906.2 THE SILVER "K" TYPE EXTINGUISHER IN THE BACK KITCHEN NEEDS TO HAVE A CURRENT INSPECTION TAG. | |
07/24/2008 | INSP - FULL | Violation | 9.) TFC 605.5 THE ORANGE EXTENSION CORD USED TO POWER THE SMALL REFRIGERATOR BEHIND THE BACK BAR IS NOT ALLOWED TO BE USED AS A SUBSTITUTE FOR PERMANENT WIRING. | |
07/24/2008 | INSP - FULL | Violation | 10.) TFC 1028. 2 THE EXIT ACCESS FROM THE BACK BAR ROOM ONTO THE BACK PATIO MUST BE KEPT UNOBSTRUCTED. ARRANGE TABLES AND POTTED PLANTS TO PROVIDE A 3 FOOT WIDE EXIT ACCESS. | |
07/24/2008 | INSP - FULL | Violation | 11.) TFC 1008.1.8.5 THE EXIT GATE FROM THE REAR PATIO NEEDS TO HAVE THE DOUBLE KEYED DEAD BOLT REPLACED WITH A THUMB TURN LATCH ON THE EGRESS SIDE. | |
07/24/2008 | INSP - FULL | Violation | 12.) TFC 315.2.1 STORAGE ON TOP OF RACK IN THE MIDDLE OF THE ROOM ON THE EAST END OF THE WINE STORAGE AREA NEEDS TO BE REMOVED TO AVOID BLOCKING SPRINKLER COVERAGE. | |
07/24/2008 | INSP - FULL | Violation | 13.) TFC 605.6 THE ELECTRICAL JUNCTION BOX IN THE CEILING NEAR THE ENTRANCE TO WINE STORAGE AREA NEEDS A COVER PLATE INSTALLED. |