Case: T08FR02059

Parcel: 10707022A


Addresses:

902 W GRANT RD

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
07/21/2008 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation.

_____ The front main entrance door secondary locking device shall be disabled or replaced to meet code standards. I.E. the lock shall release when twisted from the interior side.

1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

_____ Remove the slide bolts from the rear egress doors and/or replace with an approved locking device. If replaced, then the door shall comply with code 1008.1.8.5

1028.2 Reliability.
Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied.

1028.3 Obstructions.
A means of egress shall be free from obstructions that would prevent its use.

1028.5 Furnishings and decorations.
Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress there from, or visibility thereof.

____ Keep the west door in the main lobby free from furnishing or any other items that may block its use.