Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2009 | INSP - FULL | Approved | ||
| 07/11/2008 | INSP - FULL | Correction Required | 1) REMOVE ALL WIRING THAT IS ATTACHED TO SPRINKLER PIPING 2) STORAGE ON SHELVING SHALL BE LOWERED TO NO CLOSER THAN 18" BELOW A SPRINKLER DEFLECTOR 3) KITCHEN, RELOCATE THE DUCT WORK HANGER FROM THE SPRINKLER PIPING 4) REPLACE THE LOWER GUAGE AT THE SPRINKLER RISER. GUAGE TO BE APPROVED FOR FIRE PROTECTION. MAINTAIN A CLEAR AREA AROUND THE SPRINKLER RISER 5) PROVIDE A SIGN AT THE MAIN ENTRY, INTERIOR, " THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED" |