Case: T08FR01861

Parcel: 121070140


Addresses:

5975 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
01/22/2009 INSP - FULL Approved
07/11/2008 INSP - FULL Correction Required 1) REMOVE ALL WIRING THAT IS ATTACHED TO SPRINKLER PIPING

2) STORAGE ON SHELVING SHALL BE LOWERED TO NO CLOSER THAN 18" BELOW A SPRINKLER DEFLECTOR

3) KITCHEN, RELOCATE THE DUCT WORK HANGER FROM THE SPRINKLER PIPING

4) REPLACE THE LOWER GUAGE AT THE SPRINKLER RISER. GUAGE TO BE APPROVED FOR FIRE PROTECTION. MAINTAIN A CLEAR AREA AROUND THE SPRINKLER RISER

5) PROVIDE A SIGN AT THE MAIN ENTRY, INTERIOR, " THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED"