Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

07/11/2008

Applicant:

WONG FAMILY LTD PARTNERSHIP

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T08FR01861
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/11/2008 INSP - FULL EDESCHAI Approved 1) REMOVE ALL WIRING THAT IS ATTACHED TO SPRINKLER PIPING 2) STORAGE ON SHELVING SHALL BE LOWERED TO NO CLOSER THAN 18" BELOW A SPRINKLER DEFLECTOR 3) KITCHEN, RELOCATE THE DUCT WORK HANGER FROM THE SPRINKLER PIPING 4) REPLACE THE LOWER GUAGE AT THE SPRINKLER RISER. GUAGE TO BE APPROVED FOR FIRE PROTECTION. MAINTAIN A CLEAR AREA AROUND THE SPRINKLER RISER 5) PROVIDE A SIGN AT THE MAIN ENTRY, INTERIOR, " THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED"